FOR AIRDUCT SYSTEM.
Air duct system is a system help cool the air flow AHU (Air Handing Unit) or FCU (Fan Coil Unit) provide location needs. To keep the heat on the way, duct should be insulation material outside. NANOFLEX insulation is the optimal choice because save energy and sound-abworption, reducing noise in the system. This material prominent […]
Air duct system is a system help cool the air flow AHU (Air Handing Unit) or FCU (Fan Coil Unit) provide location needs. To keep the heat on the way, duct should be insulation material outside. NANOFLEX insulation is the optimal choice because save energy and sound-abworption, reducing noise in the system. This material prominent than fibroius material the heat by the following factors:
- Easy installation, the surface easy to clean
- High elasticity and excellent flame retardant properties.
- Enhanced ability to fight the growth of mold, bacteria
- Avoid the dangerous health, skin allergies as glass wool, rockwool fiber material causes.
- Good soundproof material, low thermal conductivity saves energy efficiency, reduce CO2
- No fiber material helps prevent the problem of potential air quality
Application NANOFLEX rubber foam for ducting works
Ambient Condition |
Operating Temperature (Cool Air Temperature) |
Remark |
|||||
200C (68.00F) |
150C (59.00F) |
130C (55.40F) |
100C (500F) |
70C (500F) |
50C (41.00F) |
||
270C(800F), 50% RH |
6mm (1/4”) |
10mm (3/8”) |
10mm (3/8”) |
13mm (1/2”) |
13mm (1/2”) |
15mm (5/8”) |
Mild Design Conditions |
300C(86.00F), 70% RH |
10mm (3/8”) |
10mm (3/8”) |
13mm (1/2”) |
13mm (1/2”) |
15mm (5/8”) |
15mm (5/8”) |
Normal Design Conditions |
320C(89.60F), 80% RH |
15mm (5/8”) |
19mm (3/4”) |
19mm (3/4”) |
19mm (3/4”) |
25mm (1”) |
28mm (1-1/8”) |
Severe Design Conditions “Like Vietnam weather” |
340C(93.20F), 85% RH |
25mm (1”) |
25mm (1”) |
25mm (1”) |
25mm (1”) |
32mm (1-1/4”) |
38mm (1-1/2”) |
“Very severe Design Conditions |
(*) Recommended thicknesses are to be used as a guide. Results are obtained under typical conditon. NANOFLEX insulation does not guarantee it will be prevent condensation. Other factors such as proper installation is crucial in condensation prevention. Please consult with our techincal staff for more precise calculations.